Electrical equipment and Class B risks

CO₂ fire extinguishers: uses, colour and safety guidance

CO₂ leaves no residue and is widely used around electrical equipment. Understand its limited cooling, re-ignition risk and important discharge precautions.

Materially reviewed: 25 August 2026Applies to: UK extinguisher identification and England fire-safety dutiesImportant: Check the label on the exact unit

Page summary

CO₂ extinguishers at a glance

The fire risk assessment should determine whether this extinguisher is appropriate, the fire rating required and where it should be positioned. Colour helps identification; it does not replace reading the label.

  • Non-conductive and leaves no residue
  • Common near electrical equipment
  • Normally carries a Class B rating
  • Limited cooling can allow re-ignition

Correct selection

What co₂ extinguishers can—and cannot—be used for

No single portable extinguisher is suitable for every fire. Use only equipment selected for the premises and only on the classes and conditions stated on its label.

Suitable where assessed
  • Energised electrical equipment where a portable extinguisher is justified
  • Class B flammable-liquid fires within the marked rating
  • Server, communications and office equipment areas
  • Clean-discharge applications where residue would cause serious damage
Do not assume it covers
  • Deep-seated Class A fires as the sole agent
  • Cooking oils and deep-fat fryers
  • Flammable gas leaks unless specifically planned and isolated
  • Combustible metals
  • Unventilated or confined spaces where gas accumulation may endanger people

How it controls fire

How a co₂ extinguisher works

Carbon dioxide reduces the local oxygen concentration around the flame and has some cooling effect as it expands. It evaporates without leaving powder, foam or water residue.

Because CO₂ provides limited cooling, hot Class A material or an unisolated energy source can re-ignite after the gas disperses. The discharge horn becomes extremely cold, and unsafe handling can cause cold burns.

Premises examples

Where this extinguisher may be considered

These are prompts for assessment, not ready-made specifications. Building use, quantities, people at risk and other protection can change the answer.

01

Offices

Frequently paired with suitable Class A provision near computers, printers and electrical equipment, with staff trained to identify the correct unit.

02

Server and communications rooms

Clean discharge can protect sensitive equipment, but room design, automatic systems, ventilation and life safety may require specialist coordination.

03

Laboratories and workshops

May cover suitable electrical or limited Class B hazards where chemical compatibility and room conditions have been assessed.

04

Retail and hospitality back-of-house areas

Can address electrical appliances, but commercial cooking-oil risks require separate Class F provision.

Before specifying equipment

Selection points that matter

Do not buy by colour or cylinder size alone. A competent selection considers the hazards, certified ratings, likely users, positioning and interaction with the emergency plan.

Re-ignition

Remove or isolate the energy source where safe. CO₂ may knock down flames without cooling the fuel enough to prevent recurrence.

Room volume

Discharge can reduce breathable oxygen. Confined and poorly ventilated spaces need particular care, warning and specialist assessment.

Horn safety

Follow the product instructions and hold only the designed insulated grip. The horn and discharge components can become cold enough to injure skin.

Rating and size

A larger cylinder is not automatically the right answer. Consider fire rating, carrying weight, discharge duration, access and likely users.

Life safety comes first

Portable extinguishers support escape; they do not make firefighting compulsory

Raise the alarm, begin the evacuation procedure and call 999. A person should only consider using an extinguisher if they have been instructed or trained, the fire is small, the correct unit is available, smoke is not affecting them and a clear escape route remains behind them. Never delay evacuation or take personal risk.

Inspection and servicing

Keep the provision usable and correctly specified

Routine checks should identify discharged, damaged, missing, obstructed or out-of-date equipment. Competent servicing should confirm condition, agent, rating, position, signage and records, while the fire risk assessment should be reviewed when hazards or layouts change.

BAFE’s SP101 scheme provides third-party certification for organisations that commission and maintain portable fire extinguishers. Certification can be useful evidence, but check that the provider’s current scope covers the work required.

Frequently asked questions

CO₂ extinguisher FAQs

What colour is a CO₂ extinguisher?

Modern UK CO₂ extinguishers normally have a red body with a black identification band. They also commonly have a distinctive discharge horn, but the label and ratings are the reliable identifiers.

What is a CO₂ fire extinguisher used for?

It is commonly selected for electrical equipment and carries a Class B rating for suitable flammable liquids. It leaves no residue, which can be valuable around sensitive equipment.

Can CO₂ be used on paper or wood?

It may temporarily suppress flames, but its limited cooling makes re-ignition of deep-seated Class A material likely. A suitably rated water-based extinguisher is normally used for that hazard.

Why should you not touch the CO₂ horn?

The discharge rapidly cools the horn and other components. Touching an uninsulated part can cause a cold burn, so users must follow the extinguisher’s handling instructions.

Is CO₂ safe in a small room?

Carbon dioxide can displace oxygen, particularly in confined or poorly ventilated spaces. People must not be placed at risk to fight a fire; evacuation and the premises emergency procedure come first.

Sources and limitations

Guidance checked against authoritative UK sources

This is general information, not an extinguisher specification or instruction to fight a fire. The selection, number, rating and position of extinguishers depend on a suitable and sufficient fire risk assessment, recognised guidance, manufacturer instructions and the actual premises.