Secondary legislation

Fire Safety (England) Regulations 2022

These regulations add specific operational and information duties for multi-occupied residential buildings. Requirements step up at above 11 metres and at the high-rise threshold of 18 metres or seven storeys.

Status: In force since 23 January 2023Applies: England onlyReviewed: 22 July 2026

Scope test

Which buildings are covered?

The regulations apply where a building contains two or more sets of domestic premises and has common parts through which residents would need to evacuate in an emergency. They principally cover purpose-built and converted blocks of flats and can include student accommodation and specialised housing.

They do not generally apply inside individual flats, except in relation to measures installed there for the safety of other residents. The responsible person under the Fire Safety Order carries the duties.

Duty matrix

What applies at each building height?

Some obligations apply to every in-scope building. The additional door-check duties begin only where the building is above 11 metres. The high-rise duties apply where the building is at least 18 metres high or has at least seven storeys.

Building categoryCore duties
All in-scope buildingsDisplay comprehensible fire-safety instructions; give them to new residents and after material changes; reissue at intervals not exceeding 12 months; provide recurring information about fire doors.
Above 11 metresUse best endeavours to check every flat entrance door at intervals not exceeding 12 months; record access attempts; check communal fire doors at least every three months.
At least 18 metres or at least 7 storeysSecure information box; electronic floor and building plans for the fire and rescue service; external-wall information; monthly checks of relevant lifts and essential firefighting equipment; wayfinding signage.

Regulation 10

Fire-door information and checks

Every resident must receive information explaining that fire doors should be kept shut when not in use, self-closing devices must not be tampered with, and faults or damage should be reported immediately. The information must be given to new residents and then at intervals not exceeding 12 months.

Above 11 metres, the recurring checks focus on whether doors are in efficient working order and good repair, including whether self-closing devices work. They are not automatically a full technical fire-door survey, but defects must be addressed and work must be competent.

  • Record each communal-door quarterly check
  • Use best endeavours and record flat access attempts
  • Check self-closing from different opening positions
  • Look for obvious damage to door, frame, glazing, seals and hardware
  • Arrange competent repair or replacement as soon as reasonably practicable

High-rise duties

Information for the fire and rescue service

For high-rise residential buildings, the responsible person must provide current electronic floor plans and a building plan, install and maintain a secure information box, and provide information about the design and materials of external walls and any material changes.

Relevant firefighting lifts, evacuation lifts and essential firefighting equipment require monthly checks. Where a fault cannot be rectified within 24 hours, it must be reported electronically to the local fire and rescue service and followed by confirmation when repaired. Wayfinding signage is also required in stairways and lobbies.

01

Plans

Keep floor and building plans accurate and supply them electronically to the local FRS.

02

Information box

Provide a secure box containing the prescribed information for firefighters.

03

External walls

Record design, materials and risk, and notify material changes.

04

Equipment

Check relevant lifts and essential firefighting equipment monthly.

Practical compliance

Build an auditable recurring programme

The regulations create recurring obligations, so a one-off FRA visit is not enough. The responsible person needs a calendar, named owners, access procedures, controlled records, escalation routes for defects and a process for reissuing resident information.

The full-FRA recording duty for all responsible persons is a separate Fire Safety Order amendment brought into force through section 156 of the Building Safety Act 2022 on 1 October 2023. It should be complied with alongside these regulations.

  • Confirm and document the height and storey calculation
  • Map each regulation to a named owner and frequency
  • Keep resident communications and delivery records
  • Control plans and external-wall information
  • Link door and equipment defects to the FRA action process

Planning inspections

Estimate a fire door survey cost

The quarterly and annual checks described in the regulations are not automatically the same as a detailed technical survey. Define the scope and use the calculator for an indicative inspection budget.

Inspection guideCost calculator

See the whole framework

Fire-safety law works as a connected system

Return to the regulations hub to compare legislation, height thresholds and voluntary standards before deciding what applies to your building.

01Regulations hub02FRA requirements03Assessment quote

Frequently asked questions

Fire Safety Regulations 2022 FAQs

Do the regulations apply below 11 metres?

Yes, if the building meets the basic multi-occupied residential scope. Resident fire-safety instructions and fire-door information apply without an 11-metre threshold.

Which fire-door checks apply above 11 metres?

Flat entrance doors must be checked at intervals not exceeding 12 months using best endeavours, with access attempts recorded. Communal fire doors must be checked at least every three months.

Is high-rise defined as both 18 metres and seven storeys?

No. A building is high-rise for these regulations if it is at least 18 metres or has at least seven storeys; either limb can bring it into scope.

Do routine door checks need a specialist?

The government guidance says the prescribed simple checks are not intended to require a specialist. Repairs, replacement and more technical inspection must nevertheless be carried out by people competent for that work.

Do these regulations require every FRA to be recorded in full?

No. That universal recording duty came from section 156 of the Building Safety Act 2022 amending the Fire Safety Order, effective 1 October 2023.

Premises-specific support

Ask what applies to your building

Tell us about the premises and the compliance question that prompted your enquiry. Your details can be reviewed and passed to a suitable fire-safety provider serving London or Surrey.

  • No obligation to book
  • Telephone number required
  • Give the building height or storeys if relevant